- SIZE: 48 x 48 (fascia) x 122.5mm (deep)
- SUPPLY: 24-230 Vac / Vdc +/- 15% 50/60Hz
- CONSUMPTION: 3W
- DISPLAY: dual 4 digits, 8 red LEDs, decimal point
- OPERATING CONDITIONS: 0-45°C, 35..95rH%
- INPUTS: 1 configurable TC K, J, S, R, PT100 (2ranges), NI100, PT1000, PT500, PTC1K, NTC10K,0-10V, 0/4-20mA, 0-40mV, Potentiometer 6KΩ / 150KΩ, TA 50mA.
- OUTPUTS: ATR243-20ABC : 2 relays 5A resistive OR 1 relay + 1 logic SSR 12V-30mA / 4..20mA / 0...10Volt for control or retransmission (4000 points accuracy), ATR243-21ABC-T : 2 relays 5A resistive + 1 logic SSR 12V-30mA / 4..20mA / 0...10Volt for control or retransmission (4000 points accuracy) + RS485 Modbus RTU (57600 baud max) + Input TA 50ma for Loop Break Alarm, ATR243-31ABC : 3 relays 5A resistive + 1 logic SSR 12V-30mA / 4..20mA / 0...10Volt for control or retransmission (4000 points accuracy) + Input TA 50ma for Loop Break Alarm
- DIGITAL INPUT: Tuning Start, Setpoint change, selection Man/Auto, Hold function, Start/Stop pre-programmed cycle
- CONTROL MODES: ON/OFF, P, PI, PID, Autotuning
- ACCURACY: 0.5% ±1digit for TC/RTD; 0.2%±1digit for V/mA
- SAMPLING TIME: selectable (max 15ms)
- SEALING: IP54 Frontal (IP65 with gasket), IP30 Box, IP20 Terminal blocks
- CONFIGURATION: Parameters protected by password, Memory card with battery for serial productions, software for parameters settings on PC.
- CERTIFICATIONS : CE CSA UL
|